If pressure gauge of the submersible pressure transmitter or level probe is selected to gauge the filling levels, this often means that the probe is used under environmental requirements which would cause failure of common level sensors.
diaphragm seal as for example soiled media, abrasive ingredients and sludge when used in wastewater treatment plants, brackish and wastewater tanks and even digester towers, impose special requirements on the design of a submersible pressure transmitter. ไดอะแฟรม of the main requirements on a submersible pressure transmitter is to have the lowest possible susceptibility to contamination or build-up of the pressure sensor by optimizing its design. This is exactly why the normal design of a pressure transmitter with narrow pressure ports isn’t used within level probes because it would tend to clog in such applications.
The look of the submersible pressure transmitter and its own pressurised sensor diaphragm is optimised in order to achieve suprisingly low susceptibility to contamination. However, continuous operation in soiled media can lead to sticking of dirt particles on the stainless diaphragm. To get the highest accuracy and fastest response times in the event of level change, the thickness of this stainless steel diaphragm has already been minimised ex factory to just a few microns. Therefore, cleaning of the diaphragm must be carried out with caution. Always avoid using sharp or edged tools. Additionally it is strongly advised never to use the popular screwdrivers or pens.
If cleaning of the sensor diaphragm is necessary, then rinse it utilizing a weak water jet or clean it carefully using compressed air. Damage of the diaphragm because of denting or notching, even though it appears to be purely superficial, results in significant losses in the accuracy of level measurement. Deformation of the diaphragm often shifts the zero point of the pressure measurement in the internal electronic measurement system and additionally distorts the output signal linearisation which has been adjusted ex works to the undamaged diaphragm. Thus, the submersible pressure transmitter with damaged diaphragm generates falsified measurement of the existing filling level and, therefore, can’t be considered a trusted measuring instrument any longer. Thus, complete replacement of the damaged instrument is absolutely necessary.
Please find further information on this topic on our information platform ?Hydrostatic level measurement?